Tables > Grounding > Conductors > Minimum size
Minimum size equipment grounding conductors for grounding raceway and equipment

Rating Or Setting Of
Automatic Overcurrent
Device In Circuit Ahead
Of Equipment, Conduit,
Etc., Not Exceeding
(Amperes)
Size
Copper
Wire No.
Aluminum Or
Copper-Clad
Aluminum
Wire No.
151412
201210
30108
40108
60108
10086
20064
30042
40031
50021/0
60012/0
8001/03/0
10002/04/0
12003/0250 kcmil
16004/0350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil800 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil

Where necessary to comply with Section 250-2(d), the equipment grounding conductor shall be sized larger than this table.
*See installation restrictions in Section 250-120.