Tables > Grounding > Conductors > Minimum size
Minimum size equipment grounding conductors for grounding raceway and equipment
|
Rating Or Setting Of Automatic Overcurrent Device In Circuit Ahead Of Equipment, Conduit, Etc., Not Exceeding (Amperes) |
| Size |
Copper Wire No. |
Aluminum Or Copper-Clad Aluminum Wire No. |
| 15 | 14 | 12 | | 20 | 12 | 10 | | 30 | 10 | 8 | | 40 | 10 | 8 | | 60 | 10 | 8 | | 100 | 8 | 6 | | 200 | 6 | 4 | | 300 | 4 | 2 | | 400 | 3 | 1 | | 500 | 2 | 1/0 | | 600 | 1 | 2/0 | | 800 | 1/0 | 3/0 | | 1000 | 2/0 | 4/0 | | 1200 | 3/0 | 250 kcmil | | 1600 | 4/0 | 350 kcmil | | 2000 | 250 kcmil | 400 kcmil | | 2500 | 350 kcmil | 600 kcmil | | 3000 | 400 kcmil | 600 kcmil | | 4000 | 500 kcmil | 800 kcmil | | 5000 | 700 kcmil | 1200 kcmil | | 6000 | 800 kcmil | 1200 kcmil |
|
Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety. | |
|