Tables > Grounding > Alternating Current > Electrode conductor
Grounding electrode conductors for alternating current systems

Size Of Largest Service-Entrance
Conductor Or Equivalent Area For
Parallel Conductors
Size Of Grounding
Electrode Conductor
Copper Aluminum Or
Copper-Clad
Aluminum
Copper *Aluminum Or
Copper-Clad
Aluminum
2 or smaller1/0 or smaller86
1 or 1/02/0 or 3/064
2/0 or 3/04/0 or 250 kcmil42
Over 3/0 thru 350 kcmilOver 250 kcmil thru 500 kcmil21/0
Over 350 kcmil thru 600 kcmilOver 500 kcmil thru 900 kcmil1/03/0
Over 600 kcmil thru 1100 kcmilOver 900 kcmil thru 1750 kcmil2/04/0
Over 1100 kcmilOver 1750 kcmil3/0250 kcmil

  1. Where multiple sets of service conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set.
  2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served.
1This table also applies to the derived conductors of separately derived ac systems.

2See installation restrictions in Section 250-64(a).

FPN: See Section 250-24(b) for size of ac system conductor brought to service equipment.

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety.
 
 
Error? Comments? Suggestions? Help us improve.
About SFASoft FAQ Disclaimer