Tables > Conductors > Dimensions and Sizes > Insulated, Fixture Wires
Dimensions of insulated conductors and fixture wires

Type Size Approx. Area
Sq. In.
RHF-2, FFH-2180.0145
RHF-2, FFH-2160.0172
RH140.0209
RH120.026
RHH, RHW, RHW-2140.0293
RHH, RHW, RHW-2120.0353
RHH, RHW, RHW-2100.0437
RHH, RHW, RHW-280.0835
RHH, RHW, RHW-260.1041
RHH, RHW, RHW-240.1333
RHH, RHW, RHW-230.1521
RHH, RHW, RHW-220.175
RHH, RHW, RHW-210.266
RHH, RHW, RHW-21/00.3039
RHH, RHW, RHW-22/00.3505
RHH, RHW, RHW-23/00.4072
RHH, RHW, RHW-24/00.4754
RHH, RHW, RHW-22500.6291
RHH, RHW, RHW-23000.7088
RHH, RHW, RHW-23500.787
RHH, RHW, RHW-24000.8626
RHH, RHW, RHW-25001.0082
RHH, RHW, RHW-26001.2135
RHH, RHW, RHW-27001.3561
RHH, RHW, RHW-27501.4272
RHH, RHW, RHW-28001.4957
RHH, RHW, RHW-29001.6377
RHH, RHW, RHW-210001.7719
RHH, RHW, RHW-212502.3479
RHH, RHW, RHW-215002.6938
RHH, RHW, RHW-217503.0357
RHH, RHW, RHW-220003.3719
SF-2, SFF-2180.0115
SF-2, SFF-2160.0139
SF-2, SFF-2140.0172
SF-1, SFF-1180.0065
RFH-1, XF, XFF180.008
TF, TFF, XF, XFF160.0109
TW, XF, XFF, THHW, THW, THW-2140.0139
TW, THHW, THW, THW-2120.0181
TW, THHW, THW, THW-2100.0243
TW, THHW, THW, THW-280.0437
RHH*, RHW*, RHW-2*140.0209
RHH*, RHW*, RHW-2*, XF, XFF120.026
RHH*, RHW*, RHW-2*, XF, XFF100.0333
RHH*, RHW*, RHW-2*80.0556
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*6.0726
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*4.0973
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*30.1134
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*20.1333
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*10.1901
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*1/00.2223
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*2/00.2624
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*3/00.3117
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*4/00.3718
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*2500.4596
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*3000.5281
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*3500.5958
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*4000.6619
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*5000.7901
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*6000.9729
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*7001.101
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*7501.1652
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*8001.2272
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*9001.3561
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*10001.4784
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*12501.8602
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*15002.1695
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*17502.4773
TW, THW, THHW, THW-2, RHH*, RHW*, RHW-2*20002.7818
TFN, TFFN180.0055
TFN, TFFN160.0072
THHN, THWN, THWN-2140.0097
THHN, THWN, THWN-2120.0133
THHN, THWN, THWN-2100.0211
THHN, THWN, THWN-280.0366
THHN, THWN, THWN-260.0507
THHN, THWN, THWN-240.0824
THHN, THWN, THWN-230.0973
THHN, THWN, THWN-220.1158
THHN, THWN, THWN-210.1562
THHN, THWN, THWN-21/00.1855
THHN, THWN, THWN-22/00.2223
THHN, THWN, THWN-23/00.2679
THHN, THWN, THWN-24/00.3237
THHN, THWN, THWN-22500.397
THHN, THWN, THWN-23000.4608
THHN, THWN, THWN-23500.5242
THHN, THWN, THWN-24000.5863
THHN, THWN, THWN-25000.7073
THHN, THWN, THWN-26000.8676
THHN, THWN, THWN-27000.9887
THHN, THWN, THWN-27501.0496
THHN, THWN, THWN-28001.1085
THHN, THWN, THWN-29001.12311
THHN, THWN, THWN-210001.3478
PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF180.0058
PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF160.0075
PF, PGFF, PGF, PFF, PTF, PAF, PTFF, PAFF, TFE, FEP, PFA, FEPB, PFAH140.01
TFE, FEP, PFA, FEPB, PFAH120.0137
TFE, FEP, PFA, FEPB, PFAH100.0191
TFE, FEP, PFA, FEPB, PFAH80.0333
TFE, FEP, PFA, FEPB, PFAH60.0468
TFE, FEP, PFA, FEPB, PFAH40.0670
TFE, FEP, PFA, FEPB, PFAH30.0804
TFE, FEP, PFA, FEPB, PFAH20.0973
TFE, PFAH10.1399
TFE, PFA, PFAH, Z1/00.1676
TFE, PFA, PFAH, Z2/00.2027
TFE, PFA, PFAH, Z3/00.2463
TFE, PFA, PFAH, Z4/00.3
ZF, ZFF180.0045
ZF, ZFF160.0061
Z, ZF, ZFF140.0083
Z120.0117
Z100.0191
Z80.0302
Z60.043
Z40.0625
Z30.0855
Z20.1029
Z10.1269
XHHW, ZW, XHHW-2, XHH140.0139
XHHW, ZW, XHHW-2, XHH120.0181
XHHW, ZW, XHHW-2, XHH100.0243
XHHW, ZW, XHHW-2, XHH80.0437
XHHW, ZW, XHHW-2, XHH60.059
XHHW, ZW, XHHW-2, XHH40.0814
XHHW, ZW, XHHW-2, XHH30.0962
XHHW, ZW, XHHW-2, XHH20.1146
XHHW, XHHW-2, XHH10.1534
XHHW, XHHW-2, XHH1/00.1825
XHHW, XHHW-2, XHH2/00.219
XHHW, XHHW-2, XHH3/00.2642
XHHW, XHHW-2, XHH4/00.3197
XHHW, XHHW-2, XHH2500.3904
XHHW, XHHW-2, XHH3000.4536
XHHW, XHHW-2, XHH3500.5166
XHHW, XHHW-2, XHH4000.5782
XHHW, XHHW-2, XHH5000.6984
XHHW, XHHW-2, XHH6000.8709
XHHW, XHHW-2, XHH7000.9923
XHHW, XHHW-2, XHH7501.0532
XHHW, XHHW-2, XHH8001.1122
XHHW, XHHW-2, XHH9001.2351
XHHW, XHHW-2, XHH10001.3519
XHHW, XHHW-2, XHH12501.718
XHHW, XHHW-2, XHH15002.0157
XHHW, XHHW-2, XHH17502.3127
XHHW, XHHW-2, XHH20002.6073
KF-2, KFF-2180.0031
KF-2, KFF-2160.0044
KF-2, KFF-2140.0064
KF-2, KFF-2120.0093
KF-2, KFF-2100.0139
KF-1, KFF-1180.0026
KF-1, KFF-1160.0037
KF-1, KFF-1140.0055
KF-1, KFF-1120.0083
KF-1, KFF-1100.0127

*Types RHH, RHW, and RHW-2 without outer covering
Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety.
 
 