Tables > Conductors > General > Conductor Properties
Wire conductor properties

Conductors DC Resistance at 75oC (167oF)
Size
AWG/kcmil
Area
Cir.
Mils
Stranding Overall Copper Aluminum
Quantity Diam.
In.
Diam.
In.
Area
In2
Uncoated
ohm/kFT
Coated
ohm/kFT
ohm/kFT
1816201-0.040.0017.778.0812.8
18162070.0150.0460.0027.958.4513.1
1625801-0.0510.0024.895.088.05
16258070.0190.0580.0034.995.298.21
1441101-0.0640.0033.073.195.06
14411070.0240.0730.0043.143.265.17
1265301-0.0810.0051.932.013.18
12653070.030.0920.0061.982.053.25
10103801-0.1020.0081.211.262
101038070.0380.1160.0111.241.292.04
8165101-0.1280.0130.7640.7861.26
81651070.0490.1460.0170.7780.8091.28
62624070.0610.1840.0270.4910.510.808
44174070.0770.2320.0420.3080.3210.508
35262070.0870.260.0530.2450.2540.403
26636070.0970.2920.0670.1940.2010.319
183690190.0660.3320.0870.1540.160.253
1/0105600190.0740.3720.1090.1220.1270.201
2/0133100190.0840.4180.1370.09670.1010.159
3/0167800190.0940.470.1730.07660.07970.126
4/0211600190.1060.5280.2190.06080.06260.1
250250000370.0820.5750.260.05150.05350.0847
300300000370.090.630.3120.04290.04460.0707
350350000370.0970.6810.3640.03670.03820.0605
400400000370.1040.7280.4160.03210.03310.0529
500500000370.1160.8130.5190.02580.02650.0424
600600000610.0990.8930.6260.02140.02230.0353
700700000610.1070.9640.730.01840.01890.0303
750750000610.1110.9980.7820.01710.01760.0282
800800000610.1141.030.8340.01610.01660.0265
900900000610.1221.0940.940.01430.01470.0235
10001000000610.1281.1521.0420.01290.01320.0212
12501250000910.1171.2891.3050.01030.01060.0169
15001500000910.1281.4121.5660.008580.008830.0141
175017500001270.1171.5261.8290.007350.007560.0121
200020000001270.1261.6322.0920.006430.006620.0106

These resistance values are valid ONLY for the parameters as given. Using conductors having coated strands, different stranding type, and, especially, other temperatures changes the resistance.
See NEC Chapter 9, Table 8.
 
 