Tables > Conductors > Ampacity > Copper, single
Allowable ampacity of single, insulated copper conductors

Ampacities Of Single Insulated Conductors Rated 0-2,000 Volts In Free Air
Based On Ambient temperature Of 30o C (86o F) Based On Ambient temperature Of 40o C (104o F)
Size 60o C
(140o F)
75o C
(167o F)
90o C
(194o F)
150o C
(302o F)
200o C
(392o F)
250o C
(482o F)
Bare
Or
Covered
Conductors
AWG
kcmil
Types
TW*,
UF*
Types
FEPW*,
RH*, RHW*,
THHW*,
THW*,
THWN*,
XHHW*,
ZW*
Types
TBS, SA,
SIS, FEP*, MI,
FEPB*, ZW-2,
RHH*, RHW-2,
THHN*, THHW*,
THW-2*, XHH,
USE-2, THWN-2*,
XHHW*,
XHHW-2
Types
Z
Types
FEP,
FEPB,
PFA
Types
PFAH,
TFE

Nickel Or
Nickel-
Coated
Copper
1425*30*35*46545930
1230*35*40*60687835
1040*50*55*809010750
860708010612414270
6809510515516520595
4105125140190220278125
3120145165214252327150
2140170190255293381175
1165195220293344440200
1/0195230260339399532235
2/0225265300390467591275
3/0260310350451546708320
4/0300360405529629830370
250340405455---415
300375445505---460
350420505570---520
400455545615---560
500515620700---635
600575690780---710
700630755855---780
750655785885---805
800680815920---835
900730870985---865
10007809351055---895
125089010651200----
150098011751325---1205
1750107012801445----
2000115513851560---1420

Overcurrent protection for conductor types marked (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper. See NEC 240-3 for motor & welders overcurrent protection exceptions.
For ambient temperatures other than those noted above, see NEC tables 310-17 & 310-19.
 
 