| Ampacities Of Single Insulated Conductors Rated 0-2,000 Volts In Free Air |
| Based On Ambient temperature Of 30o C (86o F) |
Based On Ambient temperature Of 40o C (104o F) |
| Size |
60o C (140o F) |
75o C (167o F) |
90o C (194o F) |
150o C (302o F) |
200o C (392o F) |
250o C (482o F) |
Bare Or Covered Conductors |
AWG kcmil |
Types TW*, UF* |
Types FEPW*, RH*, RHW*, THHW*, THW*, THWN*, XHHW*, ZW* |
Types TBS, SA, SIS, FEP*, MI, FEPB*, ZW-2, RHH*, RHW-2, THHN*, THHW*, THW-2*, XHH, USE-2, THWN-2*, XHHW*, XHHW-2 |
Types Z |
Types FEP, FEPB, PFA |
Types PFAH, TFE
Nickel Or Nickel- Coated Copper |
| 14 | 25* | 30* | 35* | 46 | 54 | 59 | 30 | | 12 | 30* | 35* | 40* | 60 | 68 | 78 | 35 | | 10 | 40* | 50* | 55* | 80 | 90 | 107 | 50 | | 8 | 60 | 70 | 80 | 106 | 124 | 142 | 70 | | 6 | 80 | 95 | 105 | 155 | 165 | 205 | 95 | | 4 | 105 | 125 | 140 | 190 | 220 | 278 | 125 | | 3 | 120 | 145 | 165 | 214 | 252 | 327 | 150 | | 2 | 140 | 170 | 190 | 255 | 293 | 381 | 175 | | 1 | 165 | 195 | 220 | 293 | 344 | 440 | 200 | | 1/0 | 195 | 230 | 260 | 339 | 399 | 532 | 235 | | 2/0 | 225 | 265 | 300 | 390 | 467 | 591 | 275 | | 3/0 | 260 | 310 | 350 | 451 | 546 | 708 | 320 | | 4/0 | 300 | 360 | 405 | 529 | 629 | 830 | 370 | | 250 | 340 | 405 | 455 | - | - | - | 415 | | 300 | 375 | 445 | 505 | - | - | - | 460 | | 350 | 420 | 505 | 570 | - | - | - | 520 | | 400 | 455 | 545 | 615 | - | - | - | 560 | | 500 | 515 | 620 | 700 | - | - | - | 635 | | 600 | 575 | 690 | 780 | - | - | - | 710 | | 700 | 630 | 755 | 855 | - | - | - | 780 | | 750 | 655 | 785 | 885 | - | - | - | 805 | | 800 | 680 | 815 | 920 | - | - | - | 835 | | 900 | 730 | 870 | 985 | - | - | - | 865 | | 1000 | 780 | 935 | 1055 | - | - | - | 895 | | 1250 | 890 | 1065 | 1200 | - | - | - | - | | 1500 | 980 | 1175 | 1325 | - | - | - | 1205 | | 1750 | 1070 | 1280 | 1445 | - | - | - | - | | 2000 | 1155 | 1385 | 1560 | - | - | - | 1420 |
|