Tables > Conductors > Ampacity > Copper, <=3
Allowable ampacity of no more than three copper conductors

Ampacities Of Not More Than 3 Insulated Conductors Rated 0-2,000 Volts In Raceway Or Cable
In Raceway, Cable, Or Earth, Based On
Ambient Temperature Of 30 degrees Celsius (86 degrees Fahrenheit)
In Raceway Or Cable, Based On
Ambient Temperature Of 40 degrees Celsius (104 degrees Fahrenheit)
Size 60 degrees Celsius
(140 degrees Fahrenheit)
75 degrees Celsius
(167 degrees Fahrenheit)
90 degrees Celsius
(194 degrees Fahrenheit)
150 degrees Celsius
(302 degrees Fahrenheit)
200 degrees Celsius
(392 degrees Fahrenheit)
250 degrees Celsius
(482 degrees Fahrenheit)
AWG
kcmil
Types
TW*,
UF*
Types
FEPW*,
RH*, RHW*,
THHW*,
THW*,
THWN*,
XHHW*,
USE*, ZW*
Types
TBS, SA,
SIS, FEP*, MI,
FEPB*, ZW-2,
RHH*, RHW-2,
THHN*, THHW*,
THW-2*, XHH,
USE-2, THWN-2,
XHHW*,
XHHW-2
Types
Z
Types
FEP,
FEPB,
PFA
Types
PFAH,
TFE
Nickel Or
Nickel-Coated
Copper
1420*20*25*343639
1225*25*30*434554
103035*40*556073
8405055768393
655657596110117
4708595120125148
385100110143152166
295115130160171191
1110130150186197215
1/0125150170215229244
2/0145175195251260273
3/0165200225288297308
4/0195230260332346361
250215255290---
300240285320---
350260310350---
400280335380---
500320380430---
600355420475---
700385460520---
750400475535---
800410490555---
900435520585---
1000455545615---
1250495590665---
1500520625705---
1750545650735---
2000560665750---

Overcurrent protection for conductor types market (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper. See NEC 240-2 for motor & welders overcurrent protection exceptions. See NEC 240-3D.
For ambient temperatures other than those noted above, see NEC tables 310-16 & 310-18 Footnotes.

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety.
 
 