Tables > Conductors > Ampacity > Aluminum or Copper-clad, single
Allowable ampacity of single, insulated aluminum or copper-clad aluminum conductors
|
| Ampacities Of Single Insulated Conductors Rated 0-2,000 Volts In Free Air |
| Based On Ambient Temperature Of 30 degrees Celsius (86 degrees Fahrenheit) |
Based On Ambient Temperature Of 40 degrees Celsius (104 degrees Fahrenheit) |
| Size |
60 degrees Celsius (140 degrees Fahrenheit) |
75 degrees Celsius (167 degrees Fahrenheit) |
90 degrees Celsius (194 degrees Fahrenheit) |
150 degrees Celsius (302 degrees Fahrenheit) |
AWG kcmil |
Types TW*, UF* |
Types THWN*, THHW* XHHW*, RHW*, THW*, RH* |
Types TBS, XHH, RHH*,RHW-2, XHHW*, USE-2, THHN*, SA, THHW*, THW-2, XHHW-2, ZW-2, THWN-2, SIS |
Types Z |
| 14 | - | - | - | - | | 12 | 25* | 30* | 35* | 47 | | 10 | 35* | 40* | 40* | 63 | | 8 | 45 | 55 | 60 | 83 | | 6 | 60 | 75 | 80 | 112 | | 4 | 80 | 100 | 110 | 148 | | 3 | 95 | 115 | 130 | 170 | | 2 | 110 | 135 | 150 | 198 | | 1 | 130 | 155 | 175 | 228 | | 1/0 | 150 | 180 | 205 | 263 | | 2/0 | 175 | 210 | 235 | 305 | | 3/0 | 200 | 240 | 275 | 351 | | 4/0 | 235 | 280 | 315 | 411 | | 250 | 265 | 315 | 355 | - | | 300 | 290 | 350 | 395 | - | | 350 | 330 | 395 | 445 | - | | 400 | 355 | 425 | 480 | - | | 500 | 405 | 485 | 545 | - | | 600 | 455 | 540 | 615 | - | | 700 | 500 | 595 | 675 | - | | 750 | 515 | 620 | 700 | - | | 800 | 535 | 645 | 725 | - | | 900 | 580 | 700 | 785 | - | | 1000 | 625 | 750 | 845 | - | | 1250 | 710 | 855 | 960 | - | | 1500 | 795 | 950 | 1075 | - | | 1750 | 875 | 1050 | 1185 | - | | 2000 | 960 | 1150 | 1335 | - |
|
Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety. | |
|