Tables > Conductors > Ampacity > Aluminum or Copper-clad, <= 3
Allowable ampacity of no more than three aluminum or copper-clad aluminum conductors
|
| Ampacities of not more than 3 single insulated conductors rated 0-2000 volts in raceway or cable |
In Raceway, Cable Or Earth Based On Ambient Temperature Of 30 degrees Celsius (86 degrees Fahrenheit) |
In Raceway Or Cable Based On ambient Temp Of 40 degrees Celsius (104 degrees Fahrenheit) |
| Size |
60 degrees Celsius (140 degrees Fahrenheit) |
75 degrees Celsius (167 degrees Fahrenheit) |
90 degrees Celsius (194 degrees Fahrenheit) |
150 degrees Celsius (302 degrees Fahrenheit) |
AWG kcmil |
Types TW* UF* |
Types THWN* THHW* XHHW* USE* THW* RH*, RHW* |
Types TBS, SA, SIS, THHN* THHW*, THW-2, RHH*, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 |
Types Z |
| 12 | 20* | 20* | 25* | 30 | | 10 | 25 | 30* | 35* | 44 | | 8 | 30 | 40 | 45 | 57 | | 6 | 40 | 50 | 60 | 75 | | 4 | 55 | 65 | 75 | 94 | | 3 | 65 | 75 | 85 | 109 | | 2 | 75 | 90 | 100 | 124 | | 1 | 85 | 100 | 115 | 145 | | 1/0 | 100 | 120 | 135 | 169 | | 2/0 | 115 | 135 | 150 | 198 | | 3/0 | 130 | 155 | 175 | 227 | | 4/0 | 150 | 180 | 205 | 260 | | 250 | 170 | 205 | 230 | - | | 300 | 190 | 230 | 255 | - | | 350 | 210 | 250 | 280 | - | | 400 | 225 | 270 | 305 | - | | 500 | 260 | 310 | 350 | - | | 600 | 285 | 340 | 385 | - | | 700 | 310 | 375 | 420 | - | | 750 | 320 | 385 | 435 | - | | 800 | 330 | 395 | 450 | - | | 900 | 355 | 425 | 480 | - | | 1000 | 375 | 445 | 500 | - | | 1250 | 405 | 485 | 545 | - | | 1500 | 435 | 520 | 585 | - | | 1750 | 455 | 545 | 615 | - | | 2000 | 470 | 560 | 630 | - |
|
Reprinted with permission from NFPA 70-2005, the National Electrical Code®, Copyright 2005, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety. | |
|