Tables > Transformers > Power-factor > Power-factor correction
Correcting existing power-factor to desired power-factor
Table values * KW of capacitors needed to correct from existing to desired power factor.

Existing Power Factor %
Corrected Power Factor
100% 95% 90% 85% 80% 75%
501.7321.4031.2471.1120.9820.85
521.6431.3141.1581.0230.8930.761
541.5581.2291.0730.9380.8080.676
551.5181.1891.0330.8980.7680.636
561.4791.150.9940.8590.7290.597
581.4041.0750.9190.7840.6540.522
601.3331.0040.8480.7130.5830.451
621.2650.9360.780.6450.5150.383
641.2010.8720.7160.5810.4510.319
651.1680.8390.6830.5480.4180.286
661.1390.810.6540.5190.3890.257
681.0780.7490.5930.4580.3280.196
701.020.6910.5350.40.270.138
720.9640.6350.4790.3440.2140.082
740.9090.580.4240.2890.1590.027
750.8820.5530.3970.2620.132 
760.8550.5260.370.2350.105 
780.8020.4730.3170.1820.052 
800.750.4210.2650.13  
820.6980.3690.2130.078  
840.6460.3170.161   
850.620.2910.135   
860.5940.2650.109   
880.540.2110.055   
900.4850.156    
920.4260.097    
940.3630.034    
950.329     
 
 
Error? Comments? Suggestions? Help us improve.