Tables > Motors > Ratings and Settings > Branch Circuit Protective Devices
Maximum rating or setting of branch circuit protective devices

Percent of Full-Load Current
Type of Motor Nontime Delay Fuse* Dual Element (Time-Delay) Fuse* Instantaneous Trip Breaker Inverse Time Breaker**
Single-phase motors300175800250
AC Polyphase Squirrel Cage - other than Design B energy efficient300175800250
AC Polyphase - Design B energy efficient3001751100250
Synchronous300175800250
Wound Rotor150150800150
Direct Current150150250150

For certain exceptions to the values specified, see Sections 430-52 - 430-54.
*The values in the Nontime Delay Fuse column apply to Time-Delay Class CC fuses.
**The values given in the last column also cover the ratings of nonadjustable inverse time types of circuit breakers that may be modified as in Section 430-52.
***Synchronous motors of the low-torque, low speed type (usually 450 rpm or lower), such as are used to drive reciprocating compressors, pumps, etc., that start unloaded, do not require a fuse rating or circuit-breaker setting in excess of 200% of full-load current.
 
 