Tables > Live Parts > Clearance > Minimum clearance
Minimum clearance of live parts

Nominal
Voltage
Rating
KV
Impulse Withstand
B.I.L.
KV
*Minimum Clearance Of Live Parts,
Inches
Phase-To-Phase Phase-To-Ground
Indoor Outdoor Indoors Outdoors Indoors Outdoors
2.4 - 4.1660954.573.06
7.275955.574.06
13.8951107.5125.07
14.41101109.0126.57
2312515010.5157.510
34.515015012.5159.510
 20020018.01813.013
46 200 18 13
  250 21 17
69 250 21 17
  350 31 25
115 550 53 42
138 550 53 42
  650 63 50
161 650 63 50
  750 72 58
230 750 72 58
  900 89 71
  1050 105 83

For SI units: one inch = 25.4 millimeters
*The values given are the minimum clearance for rigid parts and bare conductors under favorable service conditions. They shall be increased for conductor movement or under unfavorable service conditions, or wherever space limitations permit. The selection of the associated impulse withstand voltage for a particular system voltage is determined by the characteristics of the surge protective equipment.

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety.
 
 