Tables > Motors > Current > Full-load, Three-phase
Full-load current for three-phase alternating current motors

Induction Type Squirrel-Cage and Wound-Rotor Amperes Synchronous Type Unity Power Factor* Amperes
HP 115 Volts 200 Volts 208 Volts 230 Volts 460 Volts 575 Volts 2300 Volts 230 Volts 460 Volts 575 Volts 2300 Volts
1/24.42.52.42.21.10.9-----
3/46.43.73.53.21.61.3-----
18.44.84.64.22.11.7-----
1-1/2126.96.6632.4-----
213.67.87.56.83.42.7-----
3-1110.69.64.83.9-----
5-17.516.715.27.66.1-----
7-1/2-25.324.222119-----
10-32.230.8281411-----
15-48.346.2422117-----
20-62.159.4542722-----
25-78.274.8683427-532621-
30-9288804032-633226-
40-1201141045241-834133-
50-1501431306552-1045242-
60-177169154776216123614912
75-221211192967720155786215
100-28527324812499262021018120
125-3593433121561253125312610125
150-4143963601801443730215112130
200-5525284802401924940020116140
250----30224260----
300----36128972----
350----41433683----
400----47738295----
450----515412103----
500----590472118----

The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 volts.*For 90 and 80 percent power factor, the above figures shall be multiplied by 1.1 and 1.25 respectively.
Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the referenced subject which is represented only by the Standard in its entirety.
 
 